This paper presents a new control strategy for voltage-source converters (VSCs) in the frequency-angle domain which enables dc-link voltage regulation via frequency and load angle adjustment. A major advantage of the proposed controller is emulating the behavior of synchronous machines (SMs) with proper regulation of dc-link voltage which eases integration of VSCs interfacing distributed and renewable generation units into ac systems in the presence of conventional SMs. A cascaded frequency, angle and virtual torque control topology is developed to emulate the mechanical behavior of an SM which offers synchronization power to eliminate the need for a phase-locked-loop after initial converter synchronization, and damping power dynamics to damp power oscillations; and presents frequency dynamics similar to SMs, thus it introduces some inertia to the grid. The controller presents high stability margin and fast dc-link voltage regulation, whereas it can provide frequency support in the ac-side during contingencies. Frequency and voltage amplitude are adjusted by two separate loops. Two different variants are proposed for dc-link voltage control; namely direct dc-link voltage control and indirect dc-link voltage control via a dc-link voltage controller. Small-signal dynamics, analysis, and design process are presented. Both simulation and experimental results are provided to validate the controller effectiveness.
No takes yet. Share an insight, caveat, or question.
Ashabani et al. (2013) studied this question.