Answers are grounded in this paper and cite their sources.
This paper presents a novel structure for a three-phase four-wire (3P4W) distribution system utilizing unified power quality conditioner (UPQC). The 3P4W system is realized from a three-phase three-wire system where the neutral of series transformer used in series part UPQC is considered as the fourth wire for the 3P4W system. A new control strategy to balance the unbalanced load currents is also presented in this paper. The neutral current that may flow toward transformer neutral point is compensated by using a four-leg voltage source inverter topology for shunt part. Thus, the series transformer neutral will be at virtual zero potential during all operating conditions. The simulation results based on MATLAB/Simulink are presented to show the effectiveness of the proposed UPQC-based 3P4W distribution system.
No takes yet. Share an insight, caveat, or question.
Khadkikar et al. (2009) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: