Answers are grounded in this paper and cite their sources.
A description is given of a system used to make potential measurements in stray current areas between an underground structure and the negative bus of a railway substation. The system involved the use of two varistors with a conventional DC meter. One varistor was placed in series with the meter to block the negative potentials. The other was placed in the reverse direction across the meter to by-pass any leakage current of the first varistor. The use of four varistors with a meter is also described. 2.4.2
No takes yet. Share an insight, caveat, or question.
W. SEARLE WOODWARD (1959) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: