Answers are grounded in this paper and cite their sources.
The frequency-fixed second-order generalized integrator-based quadrature signal generator (FFSOGI-QSG) has been widely used in grid synchronization applications. The major limitations of using this technique are the unequal amplitudes of in-phase and quadrature-phase signals under grid frequency variation, which causes double-frequency oscillatory and offset errors in FFSOGI-based phase-locked loop output. To overcome the issues, in this letter, a modified complex analysis of FFSOGI-QSG using fractional-order-based conformal mapping approach has been presented, and an adaptive FFSOGI-QSG (AFFSOGI-QSG) is proposed. The proposed AFFSOGI-QSG can adapt itself to the grid frequency variations through the adjustment of single tuning parameter, i.e., fractional-order gain. The proposed structure is also found to inherit the simplicity of the FFSOGI-QSG without changing the order of the system while demonstrating an improved disturbance rejection capability under various grid disturbances. Performance of the proposed AFFSOGI-QSG is finally validated against some well-known SOGI-QSGs using numerical results obtained from the MATLAB and experimental results from the dSPACE DS1104 hardware.
No takes yet. Share an insight, caveat, or question.
Akhtar et al. (2019) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: