Answers are grounded in this paper and cite their sources.
The positive feedback-based anti-islanding scheme has become a common anti-islanding protection technique for inverter-based distributed generators (DGs). This paper investigates the scheme's impact on the small-signal stability of multiple inverter-based DGs installed in power distribution systems during grid-connected operation. The interactions among multiple-DGs due to the anti-islanding scheme are also addressed. An index is proposed to quantify the destabilizing effect of the aggregated positive feedback activities of multiple DGs. This paper further introduces a DG power transfer limit versus islanding detection time curve to reveal the conflicting requirements of anti-islanding protection speed and the maximum power transfer of multi-DG systems.
No takes yet. Share an insight, caveat, or question.
Wang et al. (2008) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: