Answers are grounded in this paper and cite their sources.
Dissolved gas analysis (DGA) has been used to classify the type and severity of faults in transformers. The method commonly used to identify severity is to measure the total fault gas concentration and its rate of change, without regard to the relative concentrations of individual gases. Thermodynamic analysis indicates that the energy required to form gases increases in the order CH42H6≤ CO ≤ C2H42≪ C2H2. Based on these results, an energy-weighted dissolved gas analysis (EWDGA) is proposed, where concentrations of individual gases are multiplied by a weighting factor that is proportional to the energy required to produce each gas. Statistical calculations are used to show that EWDGA is more sensitive to high-energy faults than simple DGA, hence minimizing the damage caused by those faults.
No takes yet. Share an insight, caveat, or question.
Noble et al. (2011) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: