This paper investigates the loss reduction potential of primary distribution systems with distributed generation (DG) units, capacitors and network reconfiguration. A methodology is proposed to combine different types of DG units and capacitors for minimising losses. A combination of reconfiguration, DG and capacitor placement to obtain high loss reduction is also presented. The results obtained on a 33-bus test distribution system with constant load condition and a 687-bus real distribution system with varying load conditions show significant loss reduction using the proposed approach. The combination of type 1 DG (i.e. DG capable of delivering real power only) and capacitor placement or reconfiguration with type 1 DG and capacitor placement can be viable for minimising losses.
No takes yet. Share an insight, caveat, or question.
Hung et al. (2013) studied this question.
Synapse has enriched 4 closely related papers on similar clinical questions. Consider them for comparative context: