The influence of the overlap length a on the no-load loss P and excitation power S of single phase model cores was measured for different sheet widths w . It was found that the optimum overlap length a 0 shows a non-linear increase with w . The appearance of such minima, however, was irregular, and in many cases, the lowest no-load loss was obtained at the smallest investigated overlap length, an effect which may result from the assembling conditions. Minima in P will appear as a consequence of a balance between loss contributions resulting from normal flux in the overlap region, from increased longitudinal flux due to flux transfer between sheets, and from the triangular cut-outs at the inner corners of the cores. However, the dependence of a 0 on w is attributed only to the triangular cut-outs. The flatness of the minima in combination with their irregular appearance, makes the effect difficult to be used in practice. It is concluded that in power transformers, the overlap length should be chosen as small as possible within the limitations set by stability requirements of the core. This is especially important in cores with a high operating flux density.