This is the authors' abstract. We don't add key points for this paper.
This paper presents a multifunctional control strategy for the autonomous operation of a multi-bus medium voltage (MV) microgrid under nonlinear and unbalanced load conditions. The main objective is to effectively compensate the harmonic currents of nonlinear loads using electronically-coupled distributed generation (DG) units. The proposed control strategy consists of a multi proportional resonant controller (MPRC) with adjustable resonance frequency and a harmonic impedance controller (HIC). The MPRC and HIC are, respectively, proposed to regulate the microgrid voltage and to share the harmonic currents of the nonlinear loads among the DG units. A conventional droop scheme is also employed to share the average powers of the loads between the DG units. Moreover, a virtual negative-sequence impedance control loop is augmented to the proposed control system to compensate the negative-sequence currents of the unbalanced loads. The proposed strategy minimizes the flow of harmonic and negative-sequence currents in the MV lines of the microgrid by local compensation of harmonic and negative-sequence currents of the feeders. The performance of the proposed control scheme is verified by using digital time-domain simulation studies in the PSCAD/EMTDC software environment.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Hamzeh et al. (2013) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: