Electrical tree initiation behavior was investigated in XLPE insulation samples made from a HVDC cable by applying constant DC and grounded DC voltages under different temperatures. No trees appeared when a constant DC voltage of -60 kV was applied for 12 days at room temperature or 20 days at 90°C, and the tree initiation time was estimated to be more than 200 days by Bayes statistical processing of zero-failure data. In the grounded DC voltage test, -15 kV prestress could trigger a tree, and under -35 kV, the tree initiation rate reached 100 %. With the increase of DC prestress, both the initiation rate and tree length increased. Grounded DC trees were branch trees with dark-colored channels, and a similar material damage could be caused by the same DC prestress. The connection of a grounding resistor could reduce the damage of sample caused by the grounded DC voltage, and the tree initiation rate declined with the increase of the resistance. According to the experimental results, the tree initiation time under constant DC voltage was not significantly shortened at 90°C, whereas tree initiation under grounded DC voltage was promoted by the increase of temperature. From 25 to 70°C, the tree branches became longer and denser, and extended in more varied directions. The observations are explained by the injection, transfer, trapping and detrapping of space charges, and charge detrapping is believed to be the cause of material damage.