This paper studies frequency regulation of power systems by using both automatic generation control (AGC) and load-side control. A switched distributed controller is designed for each load bus in a transmission network. The targets of the designed controller are twofold. First, it makes controllable loads work together with generators to restore the system frequency quickly after a real power mismatch occurs in the grid. Second, it restores controllable loads to their nominal working conditions. To achieve the first target, a consensus-based distributed load-side controller is designed. Peer-to-peer communication between loads is used to achieve an average consensus according to which controllable load reacts to the frequency deviation. To achieve the second target, the load-side controller shifts its duties to AGC slowly after the frequency goes back into an ideal region, and hence, controllable loads will restore to their nominal conditions gradually. A switching signal is designed to detect time instants when the load-side controller should work in the mode of frequency restoration or in the mode of load restoration.
No takes yet. Share an insight, caveat, or question.
Liu et al. (2016) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: