Answers are grounded in this paper and cite their sources.
Demand response has the potential to provide a multitude of operating reserve categories. However, if integrated at scale, the non-synchronous nature of most demand response sources must be recognized within the operational rules of low inertia power systems. Here, a candidate non-synchronous reserve resource is considered within the scheduling and frequency stability time frames. It is shown that a detrimental impact on the post-contingency rate of change of frequency (RoCoF) can arise-potentially requiring the development of system operator policies to ensure that security standards are not compromised-as the volume of reserve available from non-synchronous resources increases. A commitment-and-dispatch RoCoF constraint within scheduling procedures is proposed, which is independently verified using time domain simulations.
No takes yet. Share an insight, caveat, or question.
Daly et al. (2019) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: