Answers are grounded in this paper and cite their sources.
A new digital control technique is proposed to synthesize an arbitrary three‐phase PWM inverter output. Sensing two line‐to‐line voltages, the required pulse patterns for deadbeat response are computed in a real time manner based on the predicted voltage by an observer at 18‐kHz sampling frequency. When used for the uninterruptible power supply, this closed‐loop voltage control inherently results in a very low THD and a very quick transient response with less filter capacity. Also, with the repetitive compensator, the proposed scheme has advantages in improving the output waveform for nonlinear load. This paper describes the modeling technique, theoretical analysis, simulations and experimental results.
No takes yet. Share an insight, caveat, or question.
Ishihara et al. (1991) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: