Answers are grounded in this paper and cite their sources.
Power transformers are the most vital component in the electric grid. Their loss calculation is critical to transformer asset management and reflects on both operation and techno-economic assessment. Acknowledging the above, this paper presents an application of a novel loss calculation method to oil-type transformers supplying nonlinear loads. Unlike the methodology presented in std. C57.110-2018, the applied approach evaluates transformer loss components relying solely on readily available technical data. The method was experimentally validated using a full-scale 250kVA oil-type distribution transformer. Experimental results show close agreement with the theoretical model and feature errors smaller than 3%.
No takes yet. Share an insight, caveat, or question.
Miteva et al. (2025) studied this question.