The external insulation of electrical equipments is affected by the atmospheric parameters in high-altitude regions. However, there is a lack of studies conducted at the high-altitude sites of 3000 m and above worldwide so far, in contrast to many fruitful ones carried out in the artificial climate chamber. The authors investigate AC pollution flashover performance of cap-and-pin and rod insulators at high-altitude sites with a view to bridging the gap and enriching our understanding in the aspect. The AC artificial pollution tests are conducted at three high-altitude sites of 2820, 3575 and 4484 m, respectively. The results show that the exponents characterising the influence of salt deposit density, non-soluble deposit density and air pressure are 0.297–0.352, 0.122–0.142, 0.535–0.580, respectively; ambient temperature has an obvious effect on the pollution flashover voltages; there is no obvious relation between the insulator profiles and the influence exponents of salt deposit density, non-soluble deposit density, air pressure or ambient temperature.
No takes yet. Share an insight, caveat, or question.
Jiang et al. (2009) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: