When a remotely sited wind farm is connected to the utility power system through a distribution line, the overcurrent relay at the common coupling point needs a directional feature. This paper presents a method for estimating the direction of fault in such radial distribution systems using phase change in current. The difference in phase angle between the positive-sequence component of the current during fault and prefault conditions has been found to be a good indicator of the fault direction in a three-phase system. A rule base formed for the purpose decides the location of fault with respect to the relay in a distribution system. Such a strategy reduces the cost of the voltage sensor and/or connection for a protection scheme which is of relevance in emerging distributed-generation systems. The algorithm has been tested through simulation for different radial distribution systems.
No takes yet. Share an insight, caveat, or question.
Pradhan et al. (2007) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: