Answers are grounded in this paper and cite their sources.
• Compares dual-range vs conventional air supply in large spaces by CFD simulation • Dual-range supply reduces air volume for terminal devices cutting energy consumption • Optimal AC airflow saves up to 9% building energy, guiding efficient design The temperature and velocity fields of the indoor space of the stratified air-conditioning end using the dual-range air supply method and the conventional air supply method are compared using Computational Fluid Dynamics (CFD) simulation of the airflow pattern and actual measurements, with the tall space of a typical building serving as the object of analysis. The simulation results show that the dual-range supply method can effectively improve the comfort of the airnear unit's near end and enhance the environment's overall homogeneity. When horizontal side-feeding and vertical down-feeding are used together, the air volume needed for end-end operation can be decreased by approximately 39%, provided that the comfort of the air supply remains essentially the same. The optimal airflow arrangement of dispersed air conditioners can result in a combined building energy savings rate of up to 9% when compared to conventional centralized air conditioners. The study's findings can serve as a point of reference for designing architectural areas withventilation and energy efficiency.
No takes yet. Share an insight, caveat, or question.
Zhang et al. (2025) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: