Answers are grounded in this paper and cite their sources.
The insulation from six 5 kV power cables, which has been in service underground for 6 to 8 years, was examined by infrared (IR) spectroscopy and oxidation induction time (OIT) analysis. Sections of insulation containing water trees were found to contain high levels of ionic contaminants. All insulation samples showed evidence of oxidative degradation in service and frequently there was a higher than average level of oxidation in the treed regions of the insulation. Sections of the insulation containing water trees had appreciably shorter OIT's than untreed regions, indicating that they were more prone to subsequent oxidative degradation. A model for water tree formation and electrical breakdown of the insulation is described where oxidative degradation during prolonged service reduces the ability of the insulation to withstand stress concentrations at defects, and water trees are initiated. Some localized oxidation may accompany the tree propagation step. Extensive localized oxidation then takes place in the treed regions, catalyzed by ionic contaminants, and insulation failure occurs.
No takes yet. Share an insight, caveat, or question.
Garton et al. (1987) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: