Answers are grounded in this paper and cite their sources.
A new dynamic model of a three-phase three-leg transformer for steady-state and transient operating conditions is proposed in this paper. With very few exceptions, the existing models oversimplify the magnetic interactions in multileg core topologies and employ single-value nonlinear functions for modeling core nonlinearities. Unfortunately, this does not provide sufficient accuracy for a wide range of dynamic disturbances such as dc bias, ferroresonance, and inrush. For this purpose, a new time-domain model based on magnetic-circuit theory is developed to include dynamic-hysteresis behavior (major and minor loops) in asymmetric three-leg core topologies. Furthermore, a new analysis is performed to study the impacts of hysteresis on no-load and transient inrush current behavior in three-phase transformers. Simulation results have been successfully compared with measurements to verify the accuracy of the proposed model.
No takes yet. Share an insight, caveat, or question.
Moses et al. (2010) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: