Answers are grounded in this paper and cite their sources.
High fidelity numerical analyses of high-voltage gas circuit breakers have been conducted at Hitachi Energy Research with an in-house CFD-based arc simulation tool. The tool extends the capability of a commercial flow solver (ANSYS Fluent) to represent physical phenomena at play in a high voltage circuit breaker during a breaking operation, such as magnetostatics, polymeric and metal evaporation, and arc-network interaction. This work describes the implementation of the Biot-Savart law for computing the magnetic field generated by an electric arc under the magnetostatic approximation and in two--dimensional axisymmetric conditions. The implementation is compared to the reference one based on the magnetic vector potential formulation of the Amp`ere’s law in the Coulomb gauge. The limitations of the two formulations are discussed and their numerical accuracy compared.
No takes yet. Share an insight, caveat, or question.
Galletti et al. (2023) studied this question.