This is the authors' abstract. We don't add key points for this paper.
An optimal additive power control for an n-generator power system is developed that forces the system to move over optimal trajectories from appropriate initial states to a stable target state over finite time intervals [O, T]. This dynamic optimal control maintains system stability even if some of these initial states lie outside of the subspace of states leading to stable trajectories for the free-running system. Those initial states for which this technique generates admissible (or practical) controls constitutes a region of controllability. The technique presented in this paper first defines a set of admissible trajectories all originating in the designated initial state at time t = 0 and terminating in the stable target state at a fixed, arbitrary time t = T. A cost functional-defined on this set of trajectories is minimized through variational methods to yield an optimal fixed-time trajectory for the interval [0, T]. The fixed-time control required for this optimal trajectory is determined explicitly by means of the state equations. A second cost functional defined on the set of optimal fixed-time trajectories corresponding to all T ϵ(0,∞) is then minimized to generate an optimal free-time trajectory, control, and time interval [0, T*]. This minimization leads to admissible controls only for initial states in an appropriate region of controllability. Two-and four-machine examples are included for illustrating the technique.
Answers are grounded in this paper and cite their sources.
No takes yet. Share an insight, caveat, or question.
Meisel et al. (1972) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: