Simulation study demonstrates reduced peak power exceedance in power-limited grid-forming networks, suggesting lower DC-buffer requirements without triggering current limiters.
Active-power ceilings create a control challenge in droop-controlled grid-forming converter networks because the electrical response is faster than the measurements and outer control. Projected and projection-free power limiting use filtered active power in the outer power–frequency channel and therefore cannot act directly on the first electrical power peak. This paper proposes constraint-activated projection-free control, which coordinates a shaped projection-free multiplier with a bounded resistance term in the capacitor-voltage reference driven by instantaneous terminal power. A general full-order dynamic model describes the converters, controllers, and network without tying the formulation to a particular benchmark. Local well-posedness is established, and the proposed controller is shown to preserve the constrained projection-free equilibrium and active-branch Jacobian, allowing the same full-order stability assessment. Across ten tested scenarios with unchanged controller parameters, the proposed controller reduces peak power exceedance by 38.7–55.4% and accumulated excess energy by 34.1–62.2%. The corresponding DC-buffer requirement decreases without activating the independent current limiter, which isolates the source-side power constraint from AC overcurrent. A network-level study demonstrates sequential transitions between one and two constrained sources while the remaining converter supplies the feasible power imbalance. Full-order stability verification, component studies, and parameter sweeps establish the role and useful range of each controller path.
No takes yet. Share an insight, caveat, or question.
Alsaleh et al. (2026) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: