Answers are grounded in this paper and cite their sources.
A 6.6 kV single-phase fault current limiter (FCL) using a high-Tc superconducting coil as a limiting coil was developed. The development is a preliminary step to investigate the feasibility of the FCL application for high-voltage transmission lines. The FCL is of the rectifier type and is mainly comprised of a limiting coil, a sub-cooled nitrogen cryostat with a cryocooler, and a rectifier bridge. The limiting coil, wound as a solenoid by Ag/Mn sheathed Bi-2223 tapes, has an inductance of 30 mH. It is immersed in a liquid nitrogen bath in the cryostat. A Gifford-McMahon cryocooler cools the cryogen below 77.3 K. A pressure regulator keeps the cryogen at an atmospheric pressure. The coil has a critical current of 70 A at 64 K and endures a 50 Hz overvoltage of 22 kV against the ground. In a fault current limiting test with a short-circuit generator, a short-circuit current of 12.5 kA was limited to 1.2 kA.
No takes yet. Share an insight, caveat, or question.
Yazawa et al. (2001) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: