Experimental study demonstrates early prediction of electrical breakdown in point-plane gaps, indicating surges can be reliably diverted before sparking occurs.
Experiments are reported which demonstrate that the imminent electrical breakdown of a long, point-plane gap can be predicted at a sufficiently early point in time for the surge to be diverted through a bypass sphere gap. With a positive voltage surge of risetime 150 μs, imminent breakdown can be detected some 7 μs before it actually occurs, by measuring the quantity of charge injected into the gap during the breakdown corona. As a result it is possible to arrest the developing spark by triggering a bypass gap only 3 μs before breakdown would normally occur. The experiments show that the critical charge criterion is a very reliable indicator of the impending breakdown of a point-plane gap. It is possible in a series of identical surges to switch out only those which would cause breakdown of the gap if preventive action were not taken.