Answers are grounded in this paper and cite their sources.
The results of tests using a full-scale transmission line for the insulation design of the first 500-kV transmission line in Japan (the Boso Line of Tokyo Electric Power Company) are described. Having clarified the switching surge and impulse flashover characteristics of V-string insulator and strain insulator assemblies, installed on a simulated tower with a long gap of three meters or more, insulation was designed which withstands a switching surge of 2.5 per unit and is capable of unbalanced insulation between vertically arranged double circuits. The flashover path, predischarge, etc., of the switching surge was also investigated.
No takes yet. Share an insight, caveat, or question.
Saruyama et al. (1967) studied this question.