This paper presents an application of an online self-organizing fuzzy logic controller to a boiler-turbine system of a fossil power plant. The control rules and the membership functions of the proposed fuzzy logic controller are generated automatically without using a plant model. A boiler-turbine system is described as a multi-input multioutput (MIMO) nonlinear system in this paper. Then, three single-loop fuzzy logic controllers are designed independently. Simulation shows robust results for various kinds of electric load demand changes and parameter variations of boiler-turbine system.