Answers are grounded in this paper and cite their sources.
The multi infeed interaction factor (MIIF) index was introduced by CIGRE as a measure of inter-inverter interactions in multi-infeed HVDC systems, which include only line-commutated converter based HVDC (LCC-HVDC) links. The MIIF is although valid among LCCs in hybrid multi-infeed HVDC systems, but not among voltage-source converters (VSCs) as well as between LCC and VSC when the VSC operates under the constant ac voltage control mode. In this paper, a multi-infeed voltage interaction factor (MVIF) index is firstly proposed as the quantitative measure of inter-inverter interactions in hybrid multi-infeed HVDC systems. Compared to the MIIF, the MVIF is unified since it is applicable regardless of inverter types and control modes. Moreover, the quasi-steady-state power-flow model of hybrid multi-infeed HVDC systems is utilized as the mathematical framework to develop the analytical calculation method of the MVIF. This lends a theoretical basis for the efficient evaluation of inter-inverter interactions. Furthermore, the parametric dependence of the MVIF is analyzed to provide an exhaustive perspective of inter-inverter interactions. This offers a useful tool to aid planning and operation of hybrid multi-infeed HVDC systems. Finally, dynamic simulations conducted on the PSCAD/EMTDC program validate the MVIF and its analytical calculation method.
No takes yet. Share an insight, caveat, or question.
Xiao et al. (2019) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: