A diagnostic apparatus for detecting gases dissolved in transformer oil is described, in which a tetrafluoroethylene-perfluoroalkylvinylether copolymer membrane is used to separate H2 CO, CH4, C2H2, C2H4, and C2H6 from the oil. These gases are detected with a new gas detector, which consists of a catalytic gas sensor and a gas chromatograph using air as the carrier gas. Using the gas concentration, the apparatus automatically determines whether a transformer is operating normally or not and, in the latter case, what kind of fault may have occurred. By the above diagnostic apparatus, a transformer could be diagnosed simply and inexpensively. This apparatus should prove useful for identifying what kind of fault may have occurred.
No takes yet. Share an insight, caveat, or question.
Tsukioka et al. (1986) studied this question.
Synapse has enriched 3 closely related papers on similar clinical questions. Consider them for comparative context: