Answers are grounded in this paper and cite their sources.
This paper deals with the experimental investigations of particle-initiated breakdown of SF6gas stressed by the oscillating transient overvoltage and non-oscillating impulse voltages. The experiments are carried out by using hemisphere-to-plane electrodes with a needle-shaped protrusion in the gas pressure range of 0.05 to 0.3 MPa. The temporal growth of the prebreakdown process is measured by a current shunt and a photomultiplier. The electrical breakdown is initiated by the streamer corona in the vicinity of a needle-shaped protrusion and the flashover of test gap is substantially influenced by the local field enhancement due to the space charge formed by the preceding streamer corona. The dependence of the voltage-time characteristics on the polarity of test voltage is appreciable, and the minimum breakdown voltage under the damped oscillating transient overvoltage is approximately the same as that under the standard lightning impulse voltage. In presence of positive polarity, the dielectric strength of SF6gas stressed by the oscillating transient overvoltage is particularly sensitive to the local field perturbed by a sharp conducting particle. The formative time lag from the first streamer corona to breakdown is longer in negative polarity than in positive polarity and the field stabilization of space charge is more pronounced in negative polarity.
No takes yet. Share an insight, caveat, or question.
Kawamura et al. (1994) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: