Answers are grounded in this paper and cite their sources.
We proposed a circuit model of oil-immersed transformer for surge analyses in high frequency regions and evaluated its effectiveness by referring to measurement, results of a model winding. We also carried out lightning surge analyses in a 500kV substation with the new transformer model and investigated effects of transformer modeling on the lightning surge voltage at the transformer terminal. In the case of applying the new model for transformer modeling, the peak value of the surge voltage decreases but the rate of the voltage rise increases compared with the conventional transformer modeling by a concentrated capacitance element. This difference can be explained considering the charging process of capacitors in the transformer model.
No takes yet. Share an insight, caveat, or question.
Okabe et al. (1999) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: