Two electrical models of a lead–acid battery, a short-term discharge model and a long-term integrated model, were used to investigate the system performance of a battery-supported dynamic voltage restorer (DVR). The short-term model provides a simple but effective description when the DVR compensates voltage sags over a short period. The integrated model can predict accurately the terminal voltage, state of charge, battery capacity and gassing current. It gives a good description of the battery response during both discharge and charge. Parameters of both models can be determined easily from measured battery output voltages obtained from load-step tests. Both models were successfully implemented in EMTDC/PSCAD and interfaced with the digital model of a 10 kVA DVR physical prototype. They gave a very close agreement between extensive experimental data and simulation results. Application issues such as current harmonics and microcycles during charge/discharge are discussed with respect to their impact on loss of capacity and reduced lifetime of the lead–acid battery.
No takes yet. Share an insight, caveat, or question.
Zhan et al. (2003) studied this question.
Synapse has enriched 4 closely related papers on similar clinical questions. Consider them for comparative context: