Answers are grounded in this paper and cite their sources.
Studies of nonsustained disruptive discharges (NSDDs), isolated cases of which can occur in vacuum interrupters, indicate lateral discharges between the cathode and shield, which can initiate a brief discharge between the contacts. To facilitate the study of such discharges, the sample discharges were triggered by a surface discharge induced by a spark gap, built into the side of the cathode, and observed with a high-speed film camera and image-converter camera. The tests showed a cathode spot after igniting. The emitted electrons first charge the shield negatively and then are directed toward the anode. The discharge burns at a high voltage, with current ranging from 10 to 100 A. After a period of up to 400 mu s, the current demand increases abruptly; an arc discharge occurs between the contacts and discharges the capacitances near the switch. The contact gap undergoes a rapid dielectric recovery, and the restored voltage is maintained. These types of discharge were also observed with NSDDs; thus it can be assumed that the triggered discharges studied correspond to the NSDD type.>
No takes yet. Share an insight, caveat, or question.
Gebel et al. (1990) studied this question.