Tests were performed to evaluate the switching impulse (S.I.) breakdown voltage of tower window models of different sizes. Window models were tested with positive polarity S.I. and with conductor-to-structure clearances of 4.55, 5.90, 7.60 and 8.75 meters. With each size of model the 50% breakdown voltage was determined for seven different wave-fronts with a time-to-crest between 60 and 800 ps and a half-amplitude time over 3500 ps. The time-to-breakdown was also recorded and correlated to the time-to-crest of the applied wave and the breakdown voltage.