Answers are grounded in this paper and cite their sources.
Flashover tests were conducted at the Leadville EHV Test Facility of the Public Service Company of Colorado and Project EHV at Pittsfield, Mass., to obtain comparative data to evaluate the influence of air density on switching surge and impulse flashover strength of transmission line insulation. The tests showed that negative polarity flashover voltages are greater than those of positive polarity. Therefore, positive polarity will be the critical requirement for transmission line design for switching surge duty.
No takes yet. Share an insight, caveat, or question.
Phillips et al. (1967) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: