Answers are grounded in this paper and cite their sources.
Cascade control strategy has been widely used in process industry owing to its superior disturbance rejection performance over that of the standard single-loop control. Designing the cascade control system is a challenging task, especially for an unstable time-delay process. In this paper, based on the multi-scale control scheme, a new analytical tuning method is presented. The method is applicable to stable and unstable processes where it can be implemented through a fixed or variable tuning approach. In the variable tuning approach, one adjustable tuning parameter is sufficient to obtain desired cascade control performance with the aid of a set of analytical tuning formulae providing direct relationship between the controller parameters and model parameters. Meanwhile, the fixed tuning approach uses a set of empirically developed rules to determine the controller parameters. Numerical studies demonstrate the effectiveness of the proposed method compared with several established cascade control designs reported in the literature.
No takes yet. Share an insight, caveat, or question.
Jobrun Nandong (2016) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: