Answers are grounded in this paper and cite their sources.
Feasibility analysis models overvoltage stresses and insulation limits in high phase order transmission, indicating viable conductor spacing for compact power corridors.
High phase order transmission (HPO), the use of more than the conventional three phases, is a unique approach to more efficiently using the overhead transmission rights-of-way. This paper evaluates those areas which impact phase clearances and insulation requirements. Fault overvoltages, overvoltagees due to interphase coupling, switching surges, rate of rise of circuit breaker recovery voltage, and lightning performance are analyzed. Additionally, the effects of wind, ice, fault currents, and phase spacer performance on conductor spacing are considered. Representative conductor spacings and terminal insulation levels are tabulated based on the foregoing analyses.
No takes yet. Share an insight, caveat, or question.
Stewart et al. (1978) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: