A sufficiently high DC component in the current on the secondary side of a transformer causes distortion of the primary side current. Prediction of such distortion relies on the availability of magnetisation curves that extend deep enough into saturation. A simple test, carried out at rated voltage, is proposed which allows the magnetisation curve to be deduced from measured data. In addition, a systematic procedure has been developed to evaluate the primary-current distortion in both single- and three-phase transformers. Comparison between theoretical predictions and practical measurements are made, with reasonable agreement between the two.
No takes yet. Share an insight, caveat, or question.
Ahfock et al. (2006) studied this question.