Answers are grounded in this paper and cite their sources.
A method for estimating the sinusoidal iron losses of a transformer from measurements made under highly distorted voltage waveform conditions is proposed. No assumption of the hysteresis/eddy current loss division within the transformer is required. A maximum discrepancy of 2% between the corrected and actual sinusoidal measurements was obtained during the testing of a 50 kVA, 2400 V single phase transformer with voltage waveforts containing six zero crossings per period.
No takes yet. Share an insight, caveat, or question.
Arseneau et al. (1984) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: