Methods to measure the burdens of voltage transformers (VTs) and current transformers (CTs) in situ in instrument transformer test systems have been developed using non-reactive resistors connected in series with the VT secondary and in parallel with the CT secondary. This development was based on a theoretical analysis of the equivalent circuits of the instrument transformers. The burden values for the instrument transformers are obtained by measuring the ratio error (and phase displacement) with varying resistors. The values of the transformer burdens obtained using this method were consistent, within acceptable tolerances, with those measured using conventional methods.