Answers are grounded in this paper and cite their sources.
Computational modeling reveals voltage measurement errors up to ±0.213% in 220 kV gas-insulated switchgear, indicating conductor thermal expansion requires compensation.
The sliced‐electrode voltage measurement method is promising in improving high voltage measurement accuracy in gas insulated switchgear. The effect of thermal expansion on high voltage measurement accuracy has been studied. The capacitance calculation mathematical model is proposed considering effect of thermal expansion, which is used to discuss the effect of thermal expansion on capacitance. Simultaneously considered the effect of thermal and fluid fields, the temperature distribution in 220 kV GIS has been analyzed. The thermal expansion model to study expansion effect on voltage measurement accuracy is determined, in which the thermal expansion of the enclosure can be omitted, and that of the high voltage conductor is considered. The partial capacitance formula between the high voltage conductor and the sliced electrode is derived due to its thermal expansion. The relative error of measured voltage due to thermal expansion is also discussed for three different measurement schemes. Assuming temperature variation range of ±50 °C, the relative error limit is about ±0.213%. For high voltage measurement, it is important to the voltage measurement accuracy.
No takes yet. Share an insight, caveat, or question.
Zhou et al. (2026) studied this question.