Answers are grounded in this paper and cite their sources.
This study presents an investigation of the impact of the quasi‐stationary voltage support provided by a voltage source converter (VSC) connected to a single point of a power system. Based on the directional derivative concept, an analytical method is developed to quantify the sensitivities of the AC bus voltage with respect to the VSC reactive power control modes. Based on a real case study, it is shown that the method applies to VSC units that are part of VSC‐HVDC systems, which can operate in a point‐to‐point or multi‐terminal configuration. Time‐domain simulations are performed to verify the findings from the application of the analytical method on a reduced size power system.