Differences in the amount of pollution on the top and bottom surfaces of an insulator have a great influence on the DC pollution flashover voltage. Up to now, many investigations have been carried out on non-uniform pollution flashover performance of porcelain and glass insulators, but very few on composite insulators. In this paper the influence of non-uniform pollution distribution on DC composite insulators on their flashover performance was analyzed, and a correction formula for the non-uniform pollution flashover voltage was proposed, based on artificial pollution tests carried out on short samples of a composite insulator intended for ±800 kV UHVDC. The test results showed that, when the ratio (T/B) of the salt deposit density (SDD) on the top surface to that on the bottom surface is between 1/1 and 1/10, the value of the characteristic exponent a indicating the effect of SDD on the flashover voltage ranges from 0.22 to 0.255. The value of a is nearly independent of T/B. However, the flashover voltage U50decreases with the increase in T/B. The correction formula indicating the influence of non-uniform pollution distribution on the flashover voltage could be expressed as K=1 - b×log(T/B). For the tested composite insulators, the factor b was 0.141 to 0.156, which is smaller than that of porcelain or glass insulator. That is to say, the influence of T/B on the flashover voltage of the composite insulator is weaker than those on the porcelain and glass insulators.