This paper investigates the unbalanced magnetic pull acting on the turbo-generator rotor under airgap eccentric fault and rotor short circuit fault respectively. Firstly, the air-gap eccentric fault is analyzed, and the air-gap magnetic flux density of the fault is deduced, and the formula of the magnetic pull per unit area is obtained, meanwhile the unbalanced magnetic pull of x-axis and y-axis acting on the rotor are further deduced. Then, the rotor short circuit fault is analyzed and the equivalent magnetic flux method is improved. Finally, the rotor short circuit fault of a QFR-400-2-20 type generator in a power plant is investigated, and the value of the unbalanced magnetic pull is calculated by the equivalent magnetic flux method. The investigation results of this paper will be beneficial to the faults diagnosis of turbo-generator.