The very rapid dielectric breakdown of SF6 (eg, during the operation of disconnect switches in gas-insulated substations) generates steep-fronted travelling waves which couple to the exterior enclosure surface at the air/SF6 bushings and cause transient ground potential rise. These high voltage transients, which can be in the 100 kV range, propagate from the air/SF6 termination, along a transmission line defined by the bus enclosure and the ground plane, toward the switchgear. This paper presents a theoretical and experimental investigation of the phenomenon, from which the basic mechanisms have been identified.
No takes yet. Share an insight, caveat, or question.
Fujimoto et al. (1982) studied this question.