Answers are grounded in this paper and cite their sources.
Green building concept is flourishing in developing countries due to the high-energy cost. To meet the green building requirement, this paper investigate the effect of glass properties on 4 and 20 story building total, heating and cooling, loads for variable glass-wall ratios using HAP4.5 . The ratios considered are 20%, 40%, 60%, 80% & 100% glass to wall. The simulations were carried out for both building under moderate climate, Amman, Jordan was the selected city from this climatic zone. The glass overall heat transfer (U-value) & shading coefficient (S.C) are paired in nine combinations, these pairs are called Combination Number (CN). Combination Number simulate all range of glass properties, CN 1 is the worst case to 9 the best glass properties. Results showed that the minimum impact of glass properties was on 20-percentile glass to wall ratio and maximum at 100 Percentile. On the other hand, a Maximum of 10 LEED point could be achieved in the 20-percentile and 16 point in the case of 100-persentile for both 20 and 4 story building. Data found in this paper where formulated in the following equations with R2 = 0.949. 4 Story Total Load = 915514 - (63546 * CN) + (9770 * Glass to wall) 20 Story Total Load = 7638346 - (540386 * CN) + (84090 * Glass to wall)
No takes yet. Share an insight, caveat, or question.
A 2016 study studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: