Answers are grounded in this paper and cite their sources.
CF 4 is a major decomposition product of the insulating gas in C 4 F 7 N‐insulated gas‐insulated metal‐enclosed switchgear (GIS) during partial discharge or overheating faults. Its detection is essential for effective online monitoring and fault diagnosis of GIS. However, the application of photoacoustic spectroscopy for CF 4 detection is hampered by significant cross‐interference from the background C 4 F 7 N gas. In this paper, quantum chemical calculations revealed that C 4 F 7 N hydrolyses to form perfluoroisobutyrate and ammonia under base catalysis, exhibiting a low reaction energy barrier and high Gibbs free energy change, indicating ease of initiation and substantial reaction extent. This chemical specificity, unlike the stable CF 4 which does not undergo such a reaction, enables selective purification of the gas to be detected through this hydrolysis reaction. Leveraging this insight, an experimental system was constructed that cascades chemical absorption purification with photoacoustic spectroscopy detection. This system effectively mitigates the cross‐interference of C 4 F 7 N in CF 4 detection by selectively absorbing C 4 F 7 N with over 95% efficiency through a base‐catalysed nucleophilic hydrolysis reaction. This enabled the precise detection of trace amounts of CF 4 against a substantial background of C 4 F 7 N with a detection limit reaching 14.79 μL/L. This advancement offers support for the online monitoring and fault diagnosis of eco‐friendly GIS.