This paper investigates the effect of mode transition from low-frequency transverse electromagnetic (earth-return wave) to high-frequency Sommerfeld-Goubau (surface wave) propagation on switching surges in gas-insulated buses (overhead cables) by adopting complete formulas for earth-return impedance and admittance using the extended transmission line (TL) approach. The lower attenuation of the surface wave shows a significant difference in the propagation functions evaluated by the classical TL approach with Carson/;Pollaczeck's impedance and space admittance. The lower attenuation in the high-frequency region leads to a spike-like voltage at the wavefront of a step response in time domain, and results in switching surges with frequency components higher than 10 MHz. This phenomenon explains the reason why measured transient voltages and currents in gas-insulated substations show frequency components ranging from some MHz to about 100 MHz, and the transient voltages and currents are sustained for more than a few microseconds. This phenomenon cannot be reproduced by the classical TL approach. It is also verified in this paper by numerical Laplace transform and by electro-magnetic transients program simulations using the extended TL approach.
No takes yet. Share an insight, caveat, or question.
Xue et al. (2017) studied this question.
Synapse has enriched 10 related papers. Consider them for comparative context: