It is important to estimate the current magnitude and charge amount of a partial discharge (PD) in a gas‐insulated switchgear (GIS). In this study, electromagnetic fields generated by a PD in an 84 kV‐class three‐phase GIS for testing have been measured with a voltage probe installed on the outer surface of an insulation spacer of the GIS tank, and the corresponding simulations have been carried out using the three‐dimensional finite‐difference time‐domain (FDTD) method. FDTD‐computed time‐domain voltages across spacers agree reasonably well with the corresponding measured ones, and the current magnitude of PD and its charge amount have been estimated.