SF6gas has excellent dielectric strength and interrupting capability and is used in various applications such as gas insulated switchgear (GIS) in substations. However, since SF6has a high global warming potential (GWP), it is imperative to reduce its use and develop recovery technology for its reuse. This paper examined the potential of alternative insulating gases for GIS, determining experimentally the ac and lightning impulse breakdown characteristics of CO2and N2gases, which have little environmental impact, in a quasi-uniform electric field. The effect of electrode surface roughness is greater in N2than in CO2. The impulse ratio in a quasi-uniform electric field was smaller in N2than in CO2at low pressure, but this reversed when the pressure reached 1.2 MPa. The dielectric strength of an electrode with a dielectric coating was approximately equal to that of a specular-finish bare electrode in either CO2or N2when an ac voltage was applied. When lightning impulse voltage was applied, a significant improvement of dielectric strength was observed if a dielectric coating was applied to the electrode considered to be the initial electron source.
No takes yet. Share an insight, caveat, or question.
Hikita et al. (2008) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: