A general physical model of partial discharge (PD) has been developed and used to simulate discharges within a void at the tip of a metallic spike defect within a three-phase 11 kV paper insulated lead covered (PILC) cable joint. Discharges are modeled by altering surface charge density at the void boundary using a logistic function distribution. The model was validated against experimental data, and a good agreement was observed with minimal free parameters. The model was then used to investigate the impact of single phase energization on PD activity in three-phase PILC cable joints. It was concluded that PD testing of three-phase PILC cable joints should be performed at raised temperatures with the cable fully energized as this results in a higher frequency of PD activity, and reduces the level of background PD from cable terminations. This research represents a further step towards developing PD models that can describe measurements taken from operational high voltage plant.
No takes yet. Share an insight, caveat, or question.
Callender et al. (2017) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: